Hochiki Short Circuit Isolator Adaptor (Ivory) *base not included*

Part Number YBN-R/3(SCI)-OEM Categories , , ,

Talk to our specialists

Description

The YBN-R/3(SCI)-OEM is an adaptor featuring an integral short-circuit isolator, which has been designed to be fitted to a standard sensor mounting base (YBN-R/3) to convert it into a short-circuit isolator base. This combined unit will then detect and
isolate short-circuits on the loop. When a short-circuit is detected the combined unit will drop the power to the rest of the loop. The combined unit is compatible with the ESP range of sensors and does not require a loop address. A remote fire LED facility is provided when a sensor is attached to the combined unit.

NOTE: A fitted sensor will still be powered when this device is isolating.

100-2039V

EURV-SBR-IP65 Intelligent AV Wall Mounted Sounder Beacon

Available in red (100-2039V) or white (100-2039VW). The unit has a built in microphone which allows the unit to indicate a fault should the sounder not operate when activated or tested.

EVAC-RES-ISO

Dual Residential Isolator Module

The dual residential isolator module is designed to provide short circuit isolation features for Euro-VAC loops carrying Eurotech devices. It operates with Euro-VAC control panel protocol which provides for high rates of information exchange in combination with particular features that ensure fast and secure responses.

EVAC-FLR-ISO

Single Floor Isolator Module

The single floor isolator module is designed to provide short circuit isolation features for Euro-VAC loops carrying Eurotech devices. It operates with Euro-VAC control panel protocol which provides for high rates of information exchange in combination with particular features that ensure fast and secure responses.

100-2034V

EURV-OM-RM Single Relay Output Mini Module

The single output module (100-2034V) is loop-powered, designed around a fully digital protocol and provides a fast and secure response. The output channel is monitored and detects open and short circuit conditions. Connections are made using plug-in terminal blocks.