Integra Emergency Microphone Station

  • WALL MOUNT FIST MICROPHONE
  • 0, 10, 20 OR 50 SELECTION BUTTONS
  • EN54 COMPLIANT INDICATORS AND CONTROLS
  • FULLY MONITORED
  • HARDWARE BYPASS FALLBACK OPERATIOn
  • DUAL REDUNDANT OUTPUTS FOR A & BROUTERS
  • ADDITIONAL VOICE OVER IP INTERFACE, WITH POE RJ45
Part Number EMS01 Categories ,

Talk to our specialists

Description

The EMS01 Emergency Microphone Station is an EN54 compatible emergency microphone which provides All-Call functionality for making live emergency announcements to entire facilities. The microphone provides EN54 compliant emergency functions and all EN54 mandatory indicators and controls.

The microphone is housed in a lockable wall-mounting box and features a graphic LCD display together with indicators for ‘Power’, ‘Voice Alarm’, ‘System Fault’,
‘Fault’ and ‘Speak Now’. The LCD display provides remote access to the list of active faults in the PA/VA system, while the EN54 mandated control keys enable navigation through the fault list, and also provide remote fault acceptance and clearance.

The EMS01 has multiple PA/VA system interfaces. It can be connected directly to either one or two of our audio routers, enabling multiple options for system redundancy. The EMS01 will operate in an All-Call hardware bypass safety mode even in the event of processor failure within the host Voice Alarm Router.

There is also a licensed non-EN54 RJ45 Ethernet IP interface with Power over Ethernet capability for VoIP connections to our IP based PA/VA systems. All interconnect cabling and the microphone capsule is continuously monitored foropen and shortcircuits.

Top, bottom and rear cable entry points are provided by means of ‘knock-outs’ in the enclosure, while the field connections are provided by means of a set of terminals on the inside rear panel of the back box.

The EMS01 is compatible with our whole range of Voice Alarm and Public Address systems, and is designed to comply with EN54-16, ISO 7240-16 and BS5839-8. Versions with multiple PA/VA zone select buttons are also available for applications which require this.

200-210SA

Odyssey Intelligent Twin Switch Monitor

The Intelligent Twin Switch Monitor provides the function of two Switch Monitor units within one enclosure. The two units are electrically independent of each other.

200-209SA

Odyssey Intelligent Twin Input/Output Unit

The Intelligent Twin Input/Output Unit provides the function of two Input/Output Units within one enclosure. The two units are electrically independent of each other.

200-208SA

Odyssey Intelligent Mains Switching Input Output Unit

The Intelligent Mains Switching Input/Output Unit provides a single line tolerant circuit (CoreProtocol only) containing one or more normally open contacts connected to a single pair of cables. It also provides a voltage free change over relay output capable of switching mains.

200-202SA

Odyssey Intelligent Switch Monitor Module

The Intelligent Switch Monitor is designed to monitor the state of one or more single pole, volt-free contacts connected on a single pair of cables to report the status. It has a selectable status reporting delay making it suitable for monitoring flow switches.